How to Calibrate Temperature and Humidity Sensors in a Polyhouse
Polyhouse Constructions Agronomy Desk · 13 નવે, 2026
A wrong reading of even 2°C or 8–10% relative humidity (RH) can start fans too late, run foggers for too long, or hide a high-humidity disease risk. To calibrate temperature humidity sensor polyhouse equipment, first verify it against a reliable reference at crop height. Then use a simple ice-water test for temperature and a sealed saturated-salt test for RH. If the sensor or controller supports an offset, enter only the stable, repeatable error. Replace sensors that drift unpredictably or cannot be brought within their stated accuracy.
Do this check at installation, before the main summer and winter seasons, after a sensor gets wet or dusty, and whenever the readings do not match crop conditions.
Start by separating verification from calibration
Farmers often call every sensor check “calibration”. The difference matters:
- Verification means comparing the sensor with a better reference or known condition. It tells you whether there is an error.
- Calibration means adjusting the displayed reading or controller offset to correct a known error.
- Controller offset is the correction entered in a climate controller. For example, if the true temperature is 28.0°C and the installed sensor consistently shows 29.2°C, apply a -1.2°C offset where the controller allows it.
A field check does not replace laboratory calibration. But it is practical and sufficiently useful for day-to-day crop climate management. A laboratory service is worthwhile where sensor data is being used for research, compliance, a high-value nursery, or a tightly controlled fan-and-pad house.
Before testing, read the instrument manual. Some combined temperature-RH probes have no user adjustment. In that case, record the error and use it only if the controller has a separate offset setting. Do not open a sealed probe or turn internal trimmers unless the manufacturer specifically permits it.
Prepare the sensor and reference properly
Poor handling causes many false “calibration errors”. A cold probe brought into humid air can develop condensation. A probe placed near a wet wall can show high RH even though the crop zone is drier.
Use these basic items:
- The installed sensor or a removable probe.
- A trusted reference thermometer and hygrometer. Preferably use a recently checked digital instrument with stated accuracy.
- A clean insulated cup or flask, crushed ice and clean water.
- Two airtight plastic or glass containers with lids for RH checks.
- Common salt, clean water, a small cup or bottle cap, and labels.
- A notebook or phone sheet to record date, time, test condition, reference reading and sensor reading.
Allow both the reference and the sensor under test to sit together for 20–30 minutes before comparing ambient conditions. Keep them out of direct sun, away from fogger spray, cooling-pad discharge, exhaust fan air and warm electrical panels.
For routine crop-zone placement, use the principles in this guide on where to place temperature and humidity sensors in a polyhouse. Correct calibration cannot compensate for a badly located sensor.
Do a quick crop-zone comparison first
The fastest useful field check is a side-by-side comparison at the actual sensing location. It reveals whether the installed sensor is believable under normal working conditions.
How to compare readings
- Place the reference instrument and sensor under test at the same height, normally close to the crop canopy.
- Shield both from direct radiation. A white ventilated radiation shield is best. At minimum, use a clean, light-coloured ventilated cover that does not trap heat.
- Keep them at least 30–50 cm apart so they do not touch, but close enough to experience the same air.
- Stop judging immediately after a fan, fogger or vent changes state. Wait until readings settle, usually 20–30 minutes.
- Record temperature and RH every five minutes for at least three readings. Compare the average, not one fluctuating value.
If the temperature difference is steady but RH difference varies widely, look first for dirt, water droplets or poor airflow around the RH probe. RH naturally changes with temperature, so a temperature error can also contribute to an RH difference.
Test method | What it checks | Expected result or reference | Main caution |
|---|---|---|---|
Side-by-side crop-zone comparison | Normal operating accuracy | Readings should be within the combined accuracy of both instruments | Keep both probes shaded and equally ventilated |
Ice-water bath | Temperature at approximately 0°C | A stable reading close to 0°C | Keep electronics and RH sensing element dry |
Saturated sodium chloride test | RH near a stable point | About 75% RH at around 25°C | Temperature and sealed-container stability affect the result |
Second saturated-salt point | RH drift across a range | About 33% RH with magnesium chloride, if available | Use only published values for the exact salt and test temperature |
A practical farm target is to investigate a temperature difference greater than roughly 1°C or an RH difference greater than roughly 5% RH against a dependable reference. Low-cost sensors may have wider stated tolerance. Always judge against the accuracy specification of both instruments, not against an impossible expectation of zero difference.
Check temperature with the ice-water method
An ice-water mixture gives a simple, repeatable temperature point close to 0°C at normal atmospheric pressure. It is useful because ordinary room-temperature comparison can hide a sensor offset.
Step-by-step ice-point check
- Fill an insulated cup with finely crushed ice.
- Add just enough clean water to fill the spaces between the ice. There should still be plenty of ice present. A cup of only cold water is not a 0°C reference.
- Stir gently and wait two or three minutes.
- Put the temperature sensing tip only into the middle of the mixture. Do not let it touch the cup wall or bottom.
- Keep the display, cable joint and humidity sensing section above water unless the probe is rated for immersion.
- Stir gently again and wait for the reading to stabilise. This may take 3–10 minutes depending on the probe.
- Record the reading. Repeat once after removing and reinserting the probe.
A reading of 0°C is ideal, but field instruments often have a tolerance. If it repeatedly reads +1.0°C, and a side-by-side warm-air comparison also shows about +1.0°C, the offset is likely real. If the ice test is wrong but the crop-zone comparison is normal, inspect whether the probe was properly immersed or whether the response had enough time to stabilise.
Do not use ice straight from a freezer without water. Its temperature may be below 0°C. Do not use a dry block of ice either; the sensor needs good contact with the stirred ice-water mixture.
Check RH with a saturated-salt test
RH needs a different method. A sealed container holding a wet, saturated salt slurry creates a known RH after it reaches equilibrium. For a simple one-point farm check, ordinary sodium chloride (common salt) is the most accessible option.
At about 25°C, saturated sodium chloride produces roughly 75% RH. The exact RH changes slightly with temperature, salt purity and test method. Therefore, treat this as a practical check, not laboratory certification.
Make the salt test chamber
- Put 3–5 tablespoons of clean common salt in a small cup or bottle cap.
- Add a few drops of water and mix. You need a wet paste with some undissolved salt crystals still visible. If all salt dissolves, add more salt.
- Put this cup inside an airtight container. Keep the salt slurry separate from the sensor.
- Place the sensor and, if possible, the reference hygrometer in the same container without touching the wet salt.
- Seal the lid. Keep the container in a room with fairly stable temperature, away from sun.
- Leave it undisturbed for at least 6–12 hours. Larger sensors or a leaky container may need up to 24 hours.
- Note the temperature and RH without repeatedly opening the lid. If a display is outside the container, seal the cable gap carefully.
At a stable test temperature near 25°C, compare the reading with approximately 75% RH. If the sensor shows 67% RH repeatedly while a trusted reference shows 75% RH, it is reading about 8% RH low at that point.
For a stronger check, use a second known point such as saturated magnesium chloride, which is around 33% RH near 25°C. However, do not guess salt values from memory. Different salts and temperatures produce different equilibrium RH. Use a recognised reference table for the exact chemical, and use clean material. For most farms, a reliable reference comparison plus the 75% salt check is more useful than an incorrectly performed two-point test.
Never place the RH probe in direct contact with salt paste, water or condensation. Wetting the polymer sensing element can cause a temporary high reading and slow recovery.
Enter corrections carefully in the controller
Only adjust an offset when the error is consistent in more than one check. A one-time difference after fogging, irrigation or a sudden sun break is not a calibration basis.
Use this decision process:
- Stable error at ambient comparison and ice/salt test: enter an offset, if permitted.
- Small error within stated accuracy: leave the sensor unchanged, but note the result in the maintenance log.
- Error changes from test to test: clean and dry the probe, check airflow and cable connections, then retest.
- Large or continuing drift: replace the sensor or send it for service.
After applying an offset, repeat the crop-zone comparison. Check that the controller is using the corrected channel, especially where separate display and control sensors are fitted.
Avoid making large corrections based on a single 75% RH test. An RH sensor may be accurate near 75% but less accurate at 90% RH, where condensation and crop disease decisions become important. If the house frequently runs at high RH, consider a better-grade probe and periodic professional calibration.
Accurate sensors are especially important when setting fan, pad and fogger actions. See climate controller set points for fans, pads and foggers after the sensors have been checked.
Keep sensors accurate between calibration checks
Most sensor failures in Indian polyhouses are caused by dust, chemical mist, algae-laden spray, direct wetting, insects, heat radiation or cable damage—not sudden electronic failure.
Use this maintenance checklist:
- Inspect the sensor every week during peak summer, monsoon and heavy fogging periods.
- Brush loose dust gently from the protective cap. Use only the cleaning method approved by the sensor maker.
- Never blast the probe with high-pressure water or compressed air.
- Keep fogger nozzles and overhead irrigation directed away from the sensor.
- Check that the radiation shield is clean, white and open to airflow.
- Look for a cracked cable, loose terminal, corroded connector or water entry in the junction box.
- Compare installed sensors with one portable reference every month during active cropping.
- Carry out the ice-point and salt checks every 3–6 months, and after an electrical surge, prolonged condensation or repair work.
- Log every test, offset and replacement date.
In a fan-and-pad house, compare readings at similar times of day. Air close to the pad is often cooler and more humid than air near the exhaust fans. One sensor cannot represent a long house perfectly. Review how many climate sensors a polyhouse needs if different zones are behaving differently.
If your RH reading suddenly stays high after fogging, inspect the sensor before changing ventilation settings. Also check the practical methods in how to lower humidity in a polyhouse without stressing crops.
Know when cleaning is not enough
Replace or professionally service a sensor when you see any of these signs:
- Temperature or RH error is larger than the instrument specification and remains after careful retesting.
- The displayed RH stays at 0%, 100%, or one fixed value for long periods.
- Readings jump sharply while nearby reference readings are stable.
- The probe takes an unusually long time to recover after a humidity change.
- There is visible corrosion, water ingress, cracked housing or damaged cable insulation.
- The controller reports an open circuit, communication fault or implausible reading.
Keep one portable, reasonably accurate thermometer-hygrometer as a farm reference. It costs less than a crop loss caused by running fans, foggers or curtains from faulty information.
Next steps
This week, carry out a shaded side-by-side comparison in the crop zone. If the reading looks doubtful, do the ice-water temperature check and the 75% RH salt test. Record the results before entering any controller offset.
When buying or upgrading climate-control components, match sensor count and placement to house size and ventilation design. You can review protected-cultivation material through all products, or build a material kit and see current item rates for your structure. For controller wiring, sensor selection and crop-specific set points, involve a qualified automation technician or your KVK/agronomist.
Frequently asked questions
How often should I calibrate a temperature and humidity sensor in a polyhouse?
Check it against a reference monthly during an active crop, especially in summer, monsoon or frequent fogging. Do a more deliberate ice-water and RH salt check every 3–6 months, or sooner after water exposure, a power surge or suspicious readings.
Can I calibrate a combined temperature and RH sensor with only an ice bath?
No. An ice bath checks the temperature channel near 0°C but does not provide a valid humidity reference. Use a separate saturated-salt chamber or a known-good hygrometer comparison for the RH channel.
Why does my polyhouse humidity sensor show 100% RH early in the morning?
It may be real if condensation is forming, but water droplets on the sensor can also hold the reading near 100%. Check for wetting, poor airflow and location near foggers, irrigation lines or a cold surface before changing the controller setting.
Should I adjust RH calibration after every fogger cycle?
No. RH changes quickly during and after fogging, and the sensing element may need time to respond. Adjust only when repeated tests under stable conditions show the same error against a reliable reference.
Can one sensor control a large fan-and-pad polyhouse accurately?
One sensor can control basic equipment, but it may not represent all zones in a long house because conditions differ near pads, crop rows and exhaust fans. Use more sensing points or a portable audit instrument when crop response varies across the house.