Polyhouse Climate Controller Settings for Fans, Pads and Foggers
Polyhouse Constructions Agronomy Desk · 13 Nov 2026
A climate controller should bring cooling equipment on in a clear order: air movement first, then exhaust fans, then pad cooling for high heat, while foggers run only when humidity is low enough. The exact temperatures depend on crop, crop stage, outside weather and the structure. But a staged logic prevents the common problem of pads, foggers and fans operating together without benefit.
For most warm-season vegetable crops in an Indian fan-and-pad polyhouse, begin with a daytime crop-zone target around 24–28°C and relative humidity (RH) around 60–80%. Use the starting settings below only as a commissioning framework. Observe the crop and sensor readings for at least several hot afternoons before making changes.
Start with crop targets, not a single temperature
The controller reacts to air conditions; the crop reacts to leaf temperature, transpiration and root-zone water. Therefore, one fixed setting cannot suit every crop or season.
Tomato, capsicum, cucumber and flowers have different optimum ranges. Young transplants usually need gentler airflow and more stable humidity than a full-grown fruiting crop. In Maharashtra, Karnataka and Telangana summers, the outside air can be so hot that cooling pads lower indoor temperature only by a limited amount. In humid monsoon weather, pad cooling may add little cooling and can raise RH too far.
Set separate day and night programmes where the controller permits it:
- Day: manage solar heat, keep leaf temperature down and avoid excessive RH.
- Night: use the minimum ventilation needed to remove humidity and prevent condensation. Pads and foggers are normally off.
- Rain or high outdoor RH: prioritise ventilation and disease-risk control over adding moisture.
The sensor should measure the crop-zone air, not hot roof air or direct pad discharge. Read the guide on placing temperature and humidity sensors before fixing final set points.
Use this staged starting framework
For a properly designed fan-and-pad house, the first fan stage should begin before the crop gets too warm. Additional fan stages increase ventilation. Pad circulation starts only after most or all exhaust capacity is required and the air is still too hot. Fogging is a separate humidity-and-temperature tool, not an automatic companion to pad cooling.
Controller output | Starting trigger framework | Stop / lockout rule | Main purpose |
|---|---|---|---|
HAF or circulation fans | During crop hours; often continuous at low speed where variable speed is available | Can reduce or stop at cool night conditions | Mix air and reduce hot, humid pockets |
Exhaust fan stage 1 | About 1–2°C above daytime target | Stop about 1°C below its start point | First heat removal stage |
Exhaust fan stage 2 | About 2–3°C above target | Stop below stage 2 start point with deadband | Higher ventilation during rising heat |
Exhaust fan stage 3 / full ventilation | About 3–4°C above target | Remains available while pad is operating | Maximum air exchange |
Pad pump | About 1–2°C above the final fan stage, only if RH is below the selected limit | Stop below pad start point; lock out at high RH | Evaporative cooling in hot, dry weather |
Fogger | Above crop target and RH below a lower limit, usually in short cycles | Stop at upper RH limit; lock out when pads run | Add moisture and limited evaporative cooling |
For example, if a crop’s practical daytime target is 26°C, you may test fan stages at roughly 27.5°C, 29°C and 30.5°C, then permit pads around 32°C. These are not universal crop recommendations. A structure with undersized fans, poor pad area, blocked insect net or weak air circulation needs engineering correction, not artificially low controller settings. Check how to calculate exhaust fan size and how to match cooling pad area with exhaust fans if cooling is inadequate.
Set deadbands and delays to stop rapid switching
A controller needs a deadband (also called differential or hysteresis). This is the gap between an output starting and stopping. Without it, a fan or pump may switch on and off repeatedly when the reading moves around one temperature.
A useful initial approach is:
- Use about 0.5–1.5°C deadband for fan stages, depending on how quickly the house changes temperature.
- Use about 1–2°C deadband for the pad pump, so the pump does not hunt on and off.
- Use an RH differential of roughly 3–5 percentage points for fogger start and stop.
- Add a short start delay between fan stages where possible. This gives each stage time to affect the sensor reading.
- Set minimum run and off times only after checking manufacturer guidance for the fan motor, pump and controller. Excessive cycling shortens equipment life.
Do not set all fan stages at one temperature. If stage 1, stage 2 and the pad pump start together, the controller has no gradual response. It also creates a high electrical starting load.
Example of fogger RH control
Suppose the fogger is allowed only when RH is below 65%. Set it to stop at around 70% RH rather than exactly 65%. If the controller supports timed cycles, use short ON periods and longer observation periods to start with. Fine droplets should evaporate in the air; wet leaves, dripping lines or puddles mean the cycle, nozzle condition, pressure or water quality needs review.
Prevent pad and fogger conflict
The most important rule is simple: do not run foggers and cooling pads together as the normal programme. Both add water to the air. Pads normally cool a large airflow through evaporation. Foggers raise RH quickly and can reduce the pad’s ability to evaporate water.
Program an interlock such as:
- When the pad pump is ON, fogger output is OFF.
- When RH rises above the fogger upper limit, fogger output is OFF even if temperature remains high.
- When RH is high because of rain, irrigation, dense crop canopy or a wet floor, pads should be prevented from starting unless there is a separately justified emergency heat programme.
- After the pad pump stops, apply a short delay before fogging can resume. This avoids immediate changeover based on temporarily humid air near the sensor.
In hot and dry conditions, pad cooling should generally take priority in a fan-and-pad house because it treats the incoming air across the pad wall. Foggers can be useful in dry weather where pads are not running, in certain crop zones, or as a controlled humidity tool. For a full choice of system and application, see fogger vs mister for polyhouse cooling and humidity.
High humidity is not harmless. Above a crop-appropriate level, transpiration falls, condensation risk rises and fungal or bacterial disease pressure can increase. If the house is warm and already humid, the response is usually more airflow, not more fogging.
Keep HAF fans separate from exhaust fan stages
Horizontal air flow (HAF) fans mix air within the house. Exhaust fans exchange inside air with outside air. They have different jobs and should not normally share the same trigger.
Run HAF fans through the day whenever crop density and weather create uneven temperatures or humidity. A controller may run them continuously, on intervals, or at lower speed during mild conditions. At night, intermittent HAF operation can help break humid pockets, but avoid strong cold drafts over tender seedlings or flowers.
Check the crop rows, not only the controller display. If the pad-end plants are cool and wet while fan-end plants are hot, airflow balance needs attention. Correct HAF selection and layout matter as much as settings; use this guide to choose a polyhouse HAF fan.
Commission the controller with this field checklist
Do not copy settings into the controller and assume the job is complete. Test every output when the crop house is operating.
- Confirm the sensor reading. Compare the controller sensor with a reliable handheld thermometer-hygrometer at crop height. Calibrate or replace sensors that differ materially.
- Label every output. Identify HAF fans, each exhaust stage, pad pump, fogger pump, vent motors and alarms at the panel.
- Enter day and night targets. Start with the crop’s recommended range, not the maximum temperature the crop can survive.
- Enter fan stages in sequence. Check physically that each fan group starts in the intended order and rotates in the correct direction.
- Set pad permission and RH lockout. Ensure water reaches the full pad face, returns to the tank and does not flood the floor.
- Set fogger temperature, RH and cycle rules. Confirm foggers stop when pad cooling starts and when RH reaches the upper limit.
- Test alarms and failure response. Simulate a high-temperature alarm, low water level, pump fault and power-failure alert if the system provides them.
- Record readings every 30–60 minutes on a representative hot day. Note indoor temperature, RH, outdoor conditions, equipment stage, leaf condition and water use.
- Change one setting at a time. Allow one or two similar weather days before deciding whether the change helped.
A controller cannot compensate for clogged pads, scale, poor water filtration or blocked fan shutters. Include regular pad cleaning and water checks in the maintenance plan. The cellulose pad maintenance schedule explains the routine work.
Adjust settings by Indian season and crop condition
Peak summer
Start ventilation earlier in the morning as solar load rises. Pads may operate for longer in dry inland areas, but watch for reduced cooling in very hot afternoons. Use shade management, adequate irrigation and air circulation alongside controller changes. Do not keep lowering the pad start point just to chase an impossible indoor temperature.
Monsoon and humid spells
Foggers are usually unnecessary. Pad operation needs tighter RH control because outdoor air is already moisture-laden. Use exhaust and HAF fans to reduce stagnant humidity, especially after irrigation. Inspect leaves early morning for condensation.
Winter and cool nights
Disable pads and foggers unless there is a specific crop requirement. Avoid excessive exhaust operation that strips heat from the house. Instead, set a humidity-control ventilation programme that uses short, measured air exchange when RH remains high. For more detail, read how to lower humidity without stressing crops.
Dense canopy and harvest stage
As canopy closes, humidity pockets increase and airflow through rows reduces. HAF operation and night humidity control become more important. A setting that worked during early vegetative growth may need revision once the crop is tall and fruiting.
Common setting mistakes to correct immediately
- Pads start before full fan capacity: the wet pad restricts airflow and wastes water without using the system properly.
- Fogger runs at high RH: this increases leaf wetness and disease risk.
- One sensor controls a large house: conditions near the pad, centre and exhaust end can differ. Add sensors where the controller supports them.
- No deadband: pumps and motors short-cycle, causing wear and unstable climate.
- Sensor near a fogger, pad or direct sunlight: it reports a local condition, not crop-zone climate.
- No power-cut plan: fan-and-pad houses can heat rapidly in summer. Maintain alarms and backup arrangements. See heat-stress protection during power cuts.
Next steps
Write down the crop’s day and night temperature and RH range, then create a simple stage chart before programming the controller. Test it on a hot dry day and again on a humid day; the correct settings are the ones that maintain crop comfort without prolonged high RH, wet foliage or equipment short-cycling.
If you are planning or upgrading a structure, select compatible fans, pads, air circulation equipment and covering materials first. Polyhouse Constructions supplies fan-and-pad polyhouse material kits and individual components; you can build a kit and view this week’s item-wise rates before finalising the equipment layout.
Frequently asked questions
What is the best temperature setting for a polyhouse climate controller?
There is no single best number. Start from the recommended range for your crop and stage, then stage fans roughly 1–2°C apart above the daytime target. Adjust after observing crop response during both dry heat and humid weather.
Should cooling pads and foggers run at the same time?
Usually no. Both add moisture, so running them together often raises RH without giving useful extra cooling. Set a controller interlock so foggers switch off whenever the pad pump is running.
At what humidity should a polyhouse fogger stop?
The upper cut-off depends on crop and disease risk, but many vegetable programmes avoid sustained RH above roughly 75–80%. Use a start-stop differential rather than one exact RH point, and check for leaf wetness and condensation.
Why do my exhaust fans keep switching on and off?
The temperature deadband may be too narrow, the sensor may be in a poor location, or fan capacity may be too high for a small air volume at that stage. Increase the differential carefully and verify sensor readings at crop height.
Can I use the same controller settings in summer and monsoon?
No. Summer often needs more staged ventilation and evaporative cooling, while monsoon conditions require stronger humidity restraint. Review pad and fogger lockouts whenever outdoor humidity changes substantially.