How to Calculate Polyhouse Heater Capacity

Polyhouse Constructions Agronomy Desk · 13 నవం, 2026

A polyhouse heater capacity calculation estimates the useful heat output needed to hold your crop temperature on the coldest design night. Calculate heat loss through the cover, add heat loss from air leakage, then include a modest safety margin.

Use this basic equation:

Required heater output (kW) = [cover heat loss + air-leakage heat loss] × safety factor ÷ 1,000

For a single-film polyhouse, a quick starting estimate is often 120 to 220 W/m² of floor area where the night temperature difference is around 10–15°C. But do not buy a heater from this shortcut alone. The correct result can change sharply with altitude, wind, structure sealing, crop setpoint and whether a thermal curtain is used.

Start with the correct design temperature difference

The heater is selected for the largest useful temperature difference between inside and outside.

Temperature difference (ΔT) = desired inside temperature − lowest design outside temperature

For example:

  • Crop-night setpoint: 18°C
  • Lowest design outside temperature: 3°C
  • ΔT = 15°C

Do not use the average January minimum. Use a realistic low temperature for your location during the crop season. In frost-prone belts, valleys and plateau areas, the coldest night may be several degrees below the nearby town forecast. Speak with nearby growers, check local weather records where available, and plan for the night at which crop protection really matters.

The inside setpoint also depends on the crop and crop stage. A nursery, young cucumber crop or flower crop can need more protection than a mature low-temperature vegetable crop. Heating a house to 20°C when the crop can safely hold at 14–16°C greatly increases fuel use.

Measure the polyhouse heat-loss surface

Heat escapes mainly through the roof, side walls, end walls, doors and gaps. For a first calculation, measure the full covered envelope area, not only the floor area.

For a simple gable-roof polyhouse:

  1. Measure length, width, gutter height and ridge height in metres.
  2. Calculate the two sloping roof areas.
  3. Add both long side-wall areas.
  4. Add the two end-wall areas, including the triangular gable portions.
  5. Add any covered vestibule if it is heated with the main house.

Do not count the ground as a cover surface in this simple method. Soil heat exchange exists, but it changes with moisture and season. It is safer not to depend on stored soil heat when sizing a frost-protection heater.

Useful area formulas

For a gable structure:

  • Sloping roof length = √[(half width)² + (ridge height − gutter height)²]
  • Two roof areas = 2 × sloping roof length × house length
  • Side-wall area = 2 × length × gutter height
  • Two end walls = 2 × [width × gutter height + 0.5 × width × roof rise]

Multi-span houses are more complex. Measure each outer roof bay and outer wall. Internal gutters between connected bays are not exposed to outside air, so do not include them as heat-loss cover.

Choose a realistic cover heat-loss value

The heat transfer value, called the U-value, tells how much heat passes through 1 m² of material for every 1°C difference between inside and outside. Lower U-value means better insulation.

For planning, use a range rather than treating one number as exact. Film tension, wind, condensation, gaps, age of cover and installation quality all affect actual loss.

Cover or condition

Practical planning U-value (W/m²°C)

What it means for heating

Single polyfilm cover

5.5–6.5

Highest heat loss; common starting point for standard polyhouses

Double polyfilm with an inflated air gap

3.5–4.5

Lower loss, provided the air gap remains properly inflated

Single film plus properly closed night thermal screen

Often 3.5–5.0 effective range

Can cut night loss, but depends on screen coverage and edge sealing

Open nethouse or structure with open vents

Not suitable for a simple U-value calculation

Heating is normally impractical because air exchange dominates

A 250-micron white diffused film is a durable cover choice, but film thickness alone does not turn a single-layer cover into an insulated double layer. The still-air gap in a double cover or a well-sealed thermal screen makes the bigger difference.

For a naturally ventilated polyhouse, ensure side curtains, roof vents and doors close tightly before relying on a calculated capacity. Read more about the structure type in what an NVPH is and how it differs from a fan-and-pad polyhouse.

Calculate heat loss through the cover

Use this formula:

Cover heat loss (W) = cover area (m²) × U-value (W/m²°C) × ΔT (°C)

Suppose the cover area is 1,780 m², the U-value is 6 W/m²°C and ΔT is 15°C:

1,780 × 6 × 15 = 160,200 W, or 160.2 kW

This is the largest part of the heater load in a reasonably sealed single-film house. It is also why heating a tall house, or a house with a high roof-to-floor-area ratio, costs more than floor area alone suggests.

Add air-leakage heat loss

Even with vents shut, air enters around roll-up curtains, doors, insect-net interfaces, fan shutters, ridge openings and poorly sealed joints. Wind can make this loss much higher.

Calculate it with:

Air-leakage heat loss (W) = 0.33 × ACH × house volume (m³) × ΔT (°C)

Here, ACH means air changes per hour. The 0.33 factor accounts for the heat needed to warm incoming air under normal conditions.

Use a cautious ACH assumption:

House condition at night

Suggested ACH for planning

Action before increasing heater size

Very well sealed house with thermal curtain

0.25–0.5

Check curtain edges, doors and fan shutters

Standard polyhouse, vents shut

0.5–1.0

Seal side curtains, roof vents and service openings

Noticeably leaky or windy site

1.0–2.0 or more

Repair leakage; heater alone is an expensive solution

Find house volume by adding the rectangular wall volume and the roof volume. For a gable roof:

Volume = length × width × gutter height + 0.5 × length × width × roof rise

Do not use a low ACH number just to obtain a smaller heater. A heater that is adequate on a calm night but fails in wind is not adequate frost protection.

Worked example: 1,000 m² single-film polyhouse

Consider a 20 m × 50 m gable polyhouse with a 4 m gutter height and a 6 m ridge height. The target temperature is 18°C. The lowest design outside temperature is 3°C.

1. Find ΔT

18 − 3 = 15°C

2. Find cover area

Roof rise is 2 m. Half-width is 10 m.

  • Sloping roof length = √(10² + 2²) = about 10.2 m
  • Two roof areas = 2 × 10.2 × 50 = about 1,020 m²
  • Side walls = 2 × 50 × 4 = 400 m²
  • Two end walls = 2 × [(20 × 4) + (0.5 × 20 × 2)] = 200 m²
  • Total cover area = about 1,620 m²

3. Calculate cover loss

Use U = 6 W/m²°C for a planning estimate for a single-film cover.

1,620 × 6 × 15 = 145,800 W, or 145.8 kW

4. Find air volume and leakage loss

  • Rectangular volume = 20 × 50 × 4 = 4,000 m³
  • Roof volume = 0.5 × 20 × 50 × 2 = 1,000 m³
  • Total volume = 5,000 m³

Assume ACH = 0.75 for a normal closed polyhouse.

0.33 × 0.75 × 5,000 × 15 = 18,563 W, or about 18.6 kW

5. Add losses and safety factor

  • Total calculated loss = 145.8 + 18.6 = 164.4 kW
  • Add 15% reserve for wind, colder-than-expected periods and normal performance variation:
164.4 × 1.15 = 189.1 kW

Select heaters that provide about 190 kW of actual useful heat output at site conditions. Do not confuse a heater’s fuel input with its delivered output. If the supplier lists input in kW or kcal/hour, confirm the rated output and efficiency.

For this size, several staged heaters are usually more practical than one large unit. For example, two or three units allow the controller to run only the capacity needed on a mildly cold night and provide some backup if one unit stops.

Check the system, not only the heater rating

A correct kW figure can still fail if heat does not reach the crop or if the electrical and fuel system is undersized.

Use this pre-purchase checklist:

Fuel-fired heaters need special care. Use appropriately vented, approved equipment and a qualified technician. Never operate an unsuitable combustion heater in an occupied or crop-growing enclosure without proper ventilation and flue design. Incomplete combustion and exhaust gases can harm people and crops, while combustion also adds moisture that can worsen condensation and disease pressure.

For practical choices and operating points, see polyhouse heating options for winter vegetable crops and this guide on reducing winter condensation.

When the calculation needs professional review

Get a detailed heat-load design from a protected-cultivation engineer when the house is in a high-altitude or frost belt, has double layers or retractable screens, uses hot-water pipes, is a large multi-span unit, or carries high-value flowers, tissue culture plants or a nursery crop.

A detailed design can account for wind exposure, actual cover construction, pad and fan shutter leakage, pipe losses, warm-up time and zone-wise control. It is especially worthwhile when a failed night of heating could damage the whole crop.

Heating a nethouse is generally not economical because the open mesh allows continuous air exchange. If winter production needs a dependable night setpoint, use a properly enclosed polyhouse rather than trying to heat an open structure.

Next steps

First, record your lowest design night temperature, crop setpoint, structure dimensions and night sealing condition. Then calculate cover loss and leakage loss separately, and select staged heater output with a 10–25% reserve based on site uncertainty.

Before ordering, ask the heater supplier to state delivered heat output, fuel consumption at that output, electrical requirement, flue arrangement and recommended spacing. Review the structure layout and cover specification with your agronomist or protected-cultivation engineer. If you are planning the enclosure itself, you can build a material kit with live item quantities and rates before finalising the climate-control design.

Frequently asked questions

How many kW heater is needed for a 1-acre polyhouse?

There is no single acre-based answer because the crop setpoint and local minimum temperature control the load. A single-film acre house can need several hundred kW in a cold location, while a mild winter site may need far less; calculate the envelope and air-leakage losses first.

Should I size a heater using polyhouse floor area or volume?

Use both indirectly. Floor area is useful for a quick estimate, but the accurate method uses cover area for transmission loss and enclosed volume for air-leakage loss.

What safety margin should be added to the calculated heater capacity?

A 10–25% margin is commonly sensible after using realistic cover and leakage assumptions. Use the higher end for windy, frost-prone or uncertain sites, but repair obvious air leaks instead of depending only on extra heater capacity.

Can a thermal screen reduce polyhouse heater capacity?

Yes, a well-fitted night thermal screen can reduce heat loss substantially by adding resistance and reducing warm-air movement near the roof. Its actual benefit depends on complete coverage, edge sealing and disciplined closing before temperatures fall.

Why does my polyhouse remain cold even though the heater has enough kW?

Warm air may be trapped near the roof, or outside air may be entering through curtains, doors, vents and fan shutters. Check airflow circulation, sensor position, fuel supply, thermostat operation and night-time sealing before assuming the heater rating is wrong.