How to Calculate Fan and Pad Polyhouse Exhaust Fan Size

Polyhouse Constructions Agronomy Desk · 13 నవం, 2026

A correct fan and pad polyhouse exhaust fan size calculation starts with required airflow, not fan diameter or motor HP. For most Indian fan-and-pad houses, calculate the total design airflow from floor area, cross-check it with air changes per hour and heat load, then select enough fans to deliver that airflow at the actual system static pressure.

As a practical starting point, use about 140–150 m³/hour of airflow per m² of floor area for summer pad-and-fan cooling. The final requirement can be higher in very hot, dry locations, for taller houses, or where a small indoor-to-outdoor temperature difference is demanded.

Start with the three airflow calculations

Do not rely on only one formula. Each method checks a different part of the design:

Method

Formula

What it checks

Best use

Floor-area method

Airflow = floor area × 140–150 m³/hour

Standard summer ventilation capacity

Main preliminary sizing method

Air-change method

Airflow = volume × ACH

Whether air is renewed fast enough

Check for house height and volume

Heat-load method

Airflow = 3 × sensible heat load (W) ÷ permitted temperature rise (°C)

Whether airflow can remove heat

Check for local peak conditions

Use the highest reasonable result after checking assumptions. Do not add all three results together. They are alternative ways to estimate the same required airflow.

Fan-and-pad cooling works only when the fan creates a steady pressure difference across the house. It pulls outside air through the wetted cellulose pad, across the crop, and out through the exhaust fans. If airflow is low, the cool air does not reach the fan end properly. If it is too high for the pad area, air passes through too fast and pad cooling efficiency falls.

For a basic overview of this system, read what a fan and pad polyhouse is.

Step 1: Calculate airflow from polyhouse floor area

Measure the internal crop floor area:

Floor area (m²) = length (m) × width (m)

Then apply the summer airflow factor:

Required airflow (m³/hour) = floor area × 140 to 150

Use the lower end of the range only where summer conditions are relatively mild or the crop can tolerate a larger temperature rise. Use 150 m³/hour/m², or an engineer’s higher figure, in hot plains, dry summer areas and high-radiation sites.

Quick reference table

Polyhouse floor area

Total design airflow at 140 m³/hour/m²

Total design airflow at 150 m³/hour/m²

500 m²

70,000 m³/hour

75,000 m³/hour

1,000 m²

140,000 m³/hour

150,000 m³/hour

2,000 m²

280,000 m³/hour

300,000 m³/hour

4,000 m²

560,000 m³/hour

600,000 m³/hour

This is total delivered air, not the rating of one fan. For example, a 1,000 m² house needing 150,000 m³/hour may use four fans delivering roughly 37,500–40,000 m³/hour each at the design static pressure. The exact number depends on the fan performance curve, end-wall layout, available electric supply and the desired staging arrangement.

Step 2: Cross-check using polyhouse volume and air changes

The floor-area method is convenient, but an unusually tall house contains more air. Calculate the enclosed volume to ensure the chosen airflow gives sufficient air changes.

Polyhouse volume (m³) = floor area (m²) × average internal height (m)

For a simple gable or gothic structure, do not use ridge height as the average height. Average internal height is commonly between gutter height and ridge height, but the actual shape matters. Use the drawing or ask the structure designer for the internal volume when possible.

Then calculate air changes per hour:

ACH = total fan airflow (m³/hour) ÷ polyhouse volume (m³)

Or, if you have selected a target ACH:

Required airflow (m³/hour) = volume × target ACH

For summer pad-and-fan operation, a result around 25–40 air changes per hour is a useful practical check in many commercial houses. The required figure varies with house height, crop, solar load, pad length, local dry-bulb temperature and the temperature difference you accept from pad end to fan end. A short, low house may show a higher ACH for the same floor-area airflow than a tall house.

Example: 1,000 m² polyhouse

Assume a 50 m × 20 m house:

  • Floor area = 50 × 20 = 1,000 m²
  • Average internal height = 4.8 m
  • Approximate volume = 1,000 × 4.8 = 4,800 m³
  • Airflow from floor-area method = 1,000 × 150 = 150,000 m³/hour

The resulting air changes are:

150,000 ÷ 4,800 = 31.25 ACH

That is a sensible check result for a summer fan-and-pad system. If the same 1,000 m² house has a much larger volume and the result drops below the planned operating target, revisit the airflow calculation with your designer.

Step 3: Check the sensible heat load

The heat-load method is useful when designing for difficult summer conditions. It estimates how much airflow is needed to remove a known sensible heat load while allowing only a specified temperature rise from the pad end to the exhaust end.

Use this simplified relationship:

Airflow (m³/hour) = 3 × sensible heat load (W) ÷ allowed temperature rise (°C)

The factor 3 comes from the density and specific heat of air. It is suitable for preliminary calculation at normal farm conditions.

For example, suppose a thermal assessment estimates a sensible heat load of 100 kW, or 100,000 W, during a hot afternoon. If the design allows the air temperature to rise by only 2°C as it moves from cooling pad to exhaust fans:

Airflow = 3 × 100,000 ÷ 2 = 150,000 m³/hour

This agrees with the 1,000 m² example above.

A smaller permitted rise requires more airflow. At a 1°C rise, the same 100 kW load needs about 300,000 m³/hour. This is why a promise to maintain almost identical temperature throughout a long polyhouse can make the fan system impractically large.

Estimate heat load carefully

A full heat-load calculation should include solar radiation through the covering, heat transfer through the roof and walls, crop shading, internal motors and pumps, and local weather. Pad evaporation also changes the heat and moisture balance. These inputs vary sharply by month, location, film condition, shade practice and crop canopy.

For this reason, do not guess heat load from only the outdoor maximum temperature. Use the floor-area method as the starting point, and get a thermal design check for large projects, hot districts, high-value crops or sites above normal altitude.

Step 4: Select fans by delivered airflow, not catalogue airflow

After arriving at total airflow, select fans by their airflow at the design static pressure. This point is essential.

A fan may show a high airflow at zero pressure in a catalogue. But a working system has resistance from the wet pad, pad frame, shutters, insect screens if used, louvers, wind effects and duct or opening restrictions. The actual airflow is lower as static pressure rises.

Ask for the fan performance curve and confirm these points:

  1. Total required airflow: The combined delivered capacity of all operating fans should meet the calculated design airflow.
  2. Static-pressure rating: Compare fans at the expected system pressure, not at free air or zero pressure.
  3. Fan staging: Divide capacity into two or more stages. Early morning and cloudy conditions do not need every fan running.
  4. Uniform placement: Place exhaust fans along the end wall opposite the pad. Avoid leaving large dead zones at the corners.
  5. Electrical load: Check motor kW, starter or VFD requirements, cable sizing and backup arrangement before purchase. See the guide to polyhouse electricity load calculation.
  6. Service access: Fans, shutters and guards need cleaning and maintenance access from outside and inside.

Do not choose a larger motor merely because it has more HP. Fan blade design, shutter loss, pressure capability and actual performance curve decide useful air delivery.

Step 5: Match cooling-pad area to fan airflow

Fans and pads are one system. A correctly sized fan bank with an undersized pad will pull air too quickly through the pad. Water may not evaporate sufficiently, so the incoming air is warmer than expected and pressure drop rises.

Calculate pad face area as:

Pad face area (m²) = total airflow (m³/second) ÷ selected pad face velocity (m/second)

Convert hourly fan capacity first:

Airflow in m³/second = airflow in m³/hour ÷ 3,600

For the 150,000 m³/hour example:

  • Airflow = 150,000 ÷ 3,600 = 41.7 m³/second
  • At a conservative pad face velocity of 1.0 m/second, pad area = 41.7 m²
  • At 1.5 m/second, pad area = 27.8 m²

The selected face velocity depends on pad thickness, manufacturer data, water distribution and local design practice. A lower face velocity generally needs more pad area but reduces resistance and can improve contact time. Do not calculate pad length from area until the usable pad height is fixed.

For example, with a usable pad height of 1.8 m, 41.7 m² means about 23.2 m of pad length. Allow for frames, end supports and sections that are not active pad face. Read how to match cooling pad area with exhaust fans before finalising this part of the design.

Common calculation mistakes

  • Using roof area instead of crop floor area for the basic airflow calculation.
  • Selecting a fan from its zero-static-pressure rating.
  • Multiplying fan quantity by catalogue airflow without checking shutter and pad resistance.
  • Using ridge height as average height when calculating volume.
  • Designing a large fan bank but providing too little cooling pad area.
  • Fitting all fans in one stage, which causes unnecessary power use in moderate weather.
  • Ignoring power cuts. In peak summer, loss of fan operation can heat a closed house very quickly. Plan alarms, standby power and emergency ventilation. This guide explains how to prevent heat stress during power cuts.
  • Assuming fans alone solve humidity. During wet monsoon periods, outside air may already carry high moisture, so pad operation needs careful control.

Final sizing checklist

Before ordering equipment, keep these values on one drawing or calculation sheet:

  • Internal length, width, gutter height, ridge height and calculated volume
  • Crop and maximum plant height
  • Peak summer outdoor temperature and humidity for the farm location
  • Target total exhaust airflow in m³/hour
  • Air changes per hour resulting from that airflow
  • Permitted pad-to-fan temperature rise
  • Fan airflow at the specified static pressure
  • Number of fan stages and airflow per stage
  • Pad face area, thickness and selected face velocity
  • Pump, filtration, sump and water-distribution design
  • Connected electrical load, protection and power-backup plan

For material planning, build a kit with live item quantities and rates, or review exhaust fan options alongside the pad and structure specifications. Final airflow, pad and electrical drawings should be checked by a protected-cultivation engineer for your site.

Next steps

Measure the exact internal floor area and average height of your proposed house. Calculate airflow at 140–150 m³/hour per m², verify the ACH, then use the heat-load equation if your site has severe summer conditions or a strict crop-temperature target.

Next, select fans using their performance at working static pressure and size the cooling pad from the same airflow. A balanced design gives more uniform crop conditions than simply installing bigger fans.

Frequently asked questions

How many exhaust fans are needed for a 1,000 m² fan-and-pad polyhouse?

First calculate total airflow, usually around 140,000–150,000 m³/hour as a starting range. Divide this by the airflow delivered by one fan at the specified static pressure, not by its free-air catalogue rating.

Should I calculate exhaust fan capacity in CFM or m³/hour?

Either unit works, but use one unit consistently throughout the design. In India, m³/hour is convenient because polyhouse dimensions are usually measured in metres and square metres.

What happens if exhaust fan capacity is too low?

Air moves slowly from pad to fan, so the fan-end temperature rises and crop conditions become uneven. Cooling pad performance can appear poor even when the pad is properly wetted.

Can I oversize exhaust fans for better cooling?

Not without increasing pad area and checking electrical load. Excess air speed through an undersized pad reduces cooling effectiveness and can create unnecessary power consumption and drafts.

Does a taller fan-and-pad polyhouse need more fan capacity?

A taller house has more volume, so check its air changes per hour after calculating airflow from floor area. If the ACH is too low for the intended summer operation, a thermal designer may specify higher capacity or a different layout.