Where to Place Temperature and Humidity Sensors in a Polyhouse

Polyhouse Constructions Agronomy Desk · 13 ਨਵੰ 2026

A correct polyhouse temperature humidity sensor placement gives you readings that represent the crop. For most vegetable and flower crops, mount the main sensor at canopy level or about 30–60 cm above the mature crop canopy, inside a radiation shield, in a central growing zone. Keep it away from direct sun, fogger spray, side openings, cooling pads, exhaust fans and irrigation water.

The exact point changes with the structure. A naturally ventilated polyhouse can have warm and cool pockets near the sides. A fan-and-pad polyhouse has a clear gradient from the cooling pad end to the exhaust fan end. One badly located sensor can make fans, foggers or curtains operate at the wrong time.

Start with the crop zone, not a fixed height from the floor

Temperature and relative humidity (RH) can differ sharply between the roof, the crop canopy and the floor. The controller must react to conditions around leaves, flowers and fruit.

Mount the sensing element close to the top of the crop, but not inside dense foliage. As the crop grows, raise the sensor support so that it remains above the canopy.

Practical sensor height guide

Crop situation

Preferred sensor height

Why it works

Seedlings in trays or nursery benches

30–60 cm above the trays or bench canopy

Measures the air around young plants without touching foliage

Low crops such as leafy vegetables

30–50 cm above the mature canopy

Avoids the hotter roof zone and cooler moist air close to soil

Trellised tomato, capsicum, cucumber or gerbera

30–60 cm above the active canopy

Tracks the leaf-zone climate as the crop grows

Tall crop with a fixed controller sensor

Near the expected mid-to-upper canopy during the main production period

Gives more useful control than a sensor fixed at 1.5 m all season

Roof-level sensor

Only as an additional monitoring point

Useful for detecting heat buildup, but not as the only crop-control sensor

For crops that are regularly lowered, pruned or reset, review sensor height each time the canopy changes significantly. Do not let leaves cover the shield. Dense leaves hold moisture and create a small, wet microclimate that is not representative of the house.

Use a non-corroding adjustable stand, GI support, hanging wire or crop-row post. The sensor should be secure, but easy to inspect and clean.

Select a representative horizontal location

The best main location is normally in the middle third of the polyhouse length and width, over a planted bed or walkway immediately beside a representative bed. Choose an area with normal crop density and normal airflow.

Avoid placing the only sensor at a point that is unusually hot, cool, wet or draughty. A controller receiving such a reading can over-ventilate, over-fog or delay cooling for most of the crop.

Keep clear of these false-reading zones

  • Direct solar rays: A sensor in sunlight can read much warmer than the surrounding air. This is common when the sun angle changes in the morning or late afternoon.
  • Roof and gutter area: Hot air collects near the polyfilm, especially during Indian summer afternoons. A roof sensor is not a crop sensor.
  • Fogger or mister plume: Droplets wet the RH element and can show artificially high RH for several minutes or longer.
  • Drip, micro-sprinkler and hand-watering splash: Water on the sensor body affects humidity response and may damage electronics.
  • Near a cooling pad: Pad air is cooler and wetter than air in the middle or fan end of a fan-and-pad structure.
  • Directly in front of exhaust fans: Fast-moving air and the warm end of the house can give a non-representative result.
  • At side curtains, roof vents, doors or insect-net openings: Outside air enters here and changes readings quickly with wind direction.
  • Next to heaters, motors, pumps, electrical panels or CO₂ outlets: These create local heat or air movement.
  • At the end of a crop row: End rows often receive different airflow and sunlight than inner rows.

As a working rule, keep the main sensor at least 1.5–2 m away from sidewalls, doors and large ventilation openings where the structure allows. More importantly, inspect the crop zone at different times of day. If the point feels like a direct draught or receives sun, move the sensor.

Protect the sensor from sun, droplets and stagnant air

A temperature-RH sensor needs protection, but it also needs free airflow. Covering it with plastic, cloth or a closed box prevents a true reading.

Use a purpose-made white radiation shield. A multi-plate shield blocks radiant heat while allowing air to pass through. In high-radiation locations or houses with weak air movement, an aspirated shield can improve accuracy because it draws air steadily across the sensing element.

Set up the shield correctly

  1. Fit the sensor inside the radiation shield as per the manufacturer’s orientation instructions.
  2. Position the shield so it is shaded from direct sunlight throughout the day, not only at noon.
  3. Keep fogger and mister nozzles outside the zone where droplets can reach the shield opening.
  4. Mount the shield upright and level. Do not face its openings directly into a fogger line, pad airflow jet or fan discharge.
  5. Keep it clear of leaves, trellis strings and plastic mulch that may block air movement or reflect heat.
  6. Check after the first fogging cycle. If droplets collect on the shield or sensor, relocate it or alter the nozzle direction.

The shield does not make a wrong location correct. For example, a shielded sensor beside a cooling pad will still measure pad-end conditions, and a shielded sensor at the fan end will still measure warmer air.

For humid-season management, place great importance on keeping the sensor dry. A wet RH element responds slowly and can cause foggers or ventilation equipment to make poor decisions. If you use fogging for cooling, review the operating principle in this guide to fogger versus mister use in polyhouses.

Placement in naturally ventilated polyhouses and nethouses

In a naturally ventilated polyhouse (NVPH), climate varies with outdoor wind, curtain opening, roof vent design, shade, crop height and orientation. Temperature may rise in sheltered areas, while RH may be higher where air movement is weak.

Place the primary controller sensor in the central crop zone. It should not sit close to the prevailing-wind side curtain or directly under a roof vent. If the house is long, wide, partitioned, or has different crops, one central sensor is rarely enough for good monitoring.

A useful NVPH sensor layout

For a small, uniform house, start with:

  • One main control sensor in the central crop zone, at canopy height.
  • One additional monitoring sensor near the area that tends to become hottest or most humid, often a far corner or low-airflow section.
  • One outside sensor, shaded and protected from rain, if the controller uses outside conditions for automation or if you want to compare inside and outside climate.

Do not place the indoor sensor immediately behind a roll-up curtain. When curtains open, that location can suddenly read outside air rather than the average crop climate. Proper curtain operation and airflow matter as much as sensor position; see how NVPH and fan-and-pad systems differ before choosing automation logic.

For a nethouse, direct solar radiation and wind influence sensors even more. Use a radiation shield, locate the sensor within the crop rather than at the open edge, and expect readings to change faster than in a polyfilm-covered structure.

Placement in fan-and-pad polyhouses

A fan-and-pad polyhouse does not have one uniform climate. Air enters through the wet cooling pad, travels across the crop, gains heat and can lose some humidity before leaving through the exhaust fans. On hot days, the pad end is usually cooler and more humid; the fan end is usually warmer.

For this reason, do not put the only controller sensor beside the cooling pad or exhaust fan. It will not represent the entire house.

Recommended layout for fan-and-pad houses

Sensor point

Location

Main purpose

Main control sensor

Middle third of the house, at canopy level

Controls average crop-zone temperature and RH

Pad-end monitoring sensor

Several metres inside from the pad, not in direct wet airflow

Checks incoming cooled-air condition

Fan-end monitoring sensor

Several metres before the fan wall, away from direct suction

Shows the warmest end and temperature rise across the house

Outside shaded sensor

Outside the structure, sheltered from sun and rain

Compares house performance with outdoor weather

In a longer house, install more than one crop-zone monitoring point. The required count depends on house length, partitions, crop uniformity and how much climate variation you see. Read how many climate sensors a polyhouse needs when planning a larger system.

Keep pad-end and fan-end sensors separate from direct equipment influence. The pad sensor should not be wetted by droplets or installed so close that it senses only the pad face. The fan-end sensor should not be in the fan’s direct suction path, where air velocity is much higher than at crop level.

If your data consistently shows a large difference between pad and fan ends, first inspect pad wetting, fan capacity, airflow path and crop obstruction. Sensor relocation should not be used to hide a genuine cooling problem. Equipment matching is covered in this cooling pad and exhaust fan guide.

Install, test and maintain the sensor

Good placement is confirmed with field checks, not just a drawing. Install the sensor before the crop is fully established if possible, then revisit it as the canopy develops.

Site-check checklist

After installation, log readings during early morning, noon, late afternoon and a fogging or cooling cycle. Walk through the house with a portable temperature-RH meter. If the fixed sensor is consistently unlike most crop rows, shift it to a more representative point or add zone sensors.

Clean dust, algae, insect webbing and mineral deposits from the radiation shield. Do not wash an electronic sensor unless its ingress-protection rating permits it. Check accuracy at the supplier’s recommended interval, and especially before summer and before the humid monsoon crop period. A practical procedure is explained in calibrating polyhouse RH sensors.

Use readings for decisions, not just display

Sensor placement has value only when the reading leads to an appropriate action. Set fan, pad, curtain, fogger and alarm controls using crop stage, local weather and the measured conditions at canopy level.

Avoid using RH alone. The same RH can mean different plant stress at different temperatures. Where your controller supports it, temperature and RH can also be used to assess vapour pressure deficit (VPD), which better describes the drying demand around leaves. Learn the basics in using VPD for polyhouse climate management.

Keep a simple record of sensor readings, outside weather, equipment running time and crop symptoms. Condensation, wet foliage in the morning, leaf-edge burn or uneven fruit set may reveal climate zones that a single sensor misses.

Next steps

Mark the middle crop zone on your layout, then mount the main temperature-RH sensor 30–60 cm above the mature canopy with a radiation shield. Run the house through a sunny afternoon and one fogging or cooling cycle, and check that neither sun nor water reaches the sensor.

For a fan-and-pad polyhouse, add pad-end and fan-end monitoring points before relying on one controller reading. If you are planning the structure, cooling equipment or climate-control layout, review relevant material options through the Polyhouse Constructions product range and build a material list with the live kit builder.

Frequently asked questions

Can I place a temperature and humidity sensor at 1.5 m height in every polyhouse?

It can work for some mature vegetable crops, but a fixed 1.5 m height is not correct for every crop stage. The better rule is to keep the sensor about 30–60 cm above the active canopy and adjust it as the crop grows.

Should the sensor be placed above or below a fogger line?

Neither position is suitable if fog droplets can reach the sensor or enter its radiation shield. Place it outside the wetted zone and confirm this by watching at least one complete fogging cycle.

Why does my polyhouse RH sensor show 95–100% humidity just after fogging?

The sensor may be detecting droplets on its sensing element rather than only water vapour in the air. Check for direct spray, splash, dripping from the roof or a dirty radiation shield, and allow the sensor to dry before judging its accuracy.

Do I need a separate outside temperature and humidity sensor?

An outside sensor is very useful for comparing inside and outside climate and for advanced controller logic. Mount it in a shaded, ventilated and rain-protected position, away from hot walls, concrete and exhaust discharge.

Where should I put the sensor in a polyhouse with two different crops?

Each crop zone should have its own monitoring sensor because canopy height, transpiration and climate needs can differ. If one controller operates both zones, use the crop with the stricter climate requirement as the control reference or create separate control zones where practical.