How to Match Cooling Pad Area With Exhaust Fans
Polyhouse Constructions Agronomy Desk · १३ नोव्हें, २०२६
A correctly sized cooling pad lets all exhaust fans pull air through the wet cellulose evenly. The simple calculation is:
Required active cooling pad area (m²) = total fan airflow (m³/s) ÷ chosen pad face velocity (m/s).
For many fan-and-pad polyhouses using cellulose pads, a practical starting target is about 1.0–1.5 m/s pad face velocity. Use the lower end where summer heat is severe, the pad is thick, water quality is difficult, or you need more stable cooling. Use the fan’s airflow at its working static pressure—not its free-air catalogue number.
For example, if all operating exhaust fans together deliver 45,000 m³/hour, that is 12.5 m³/s. At a target pad velocity of 1.25 m/s, you need 10 m² of active pad face area.
Start With the Two Numbers That Matter
You need only two design inputs before calculating cooling pad area for an exhaust fan system:
- Actual total exhaust airflow, in m³/hour or m³/s.
- Target air velocity through the pad face, in m/s.
The calculation applies to a fan-and-pad polyhouse with cooling pads installed along one end wall or on side walls and exhaust fans at the opposite end. It is not the sizing method for a naturally ventilated structure. If you are still comparing systems, see NVPH versus fan-and-pad polyhouse.
1. Use actual fan capacity, not the number on the fan box
Add the airflow of every exhaust fan that will run together during peak summer cooling. But use airflow at the expected operating static pressure. Fans move less air once they pull through wet pads, insect screens, shutters, louvers and a crop canopy.
Ask the supplier for the fan performance curve or technical data. Select the airflow value at the system’s estimated resistance. If that figure is unavailable, avoid treating a free-air rating as guaranteed delivered airflow. The final pad area can otherwise be too small.
For a new structure, first establish the needed ventilation rate and fan quantity. This is covered in how to calculate polyhouse exhaust fan size. Once the fans are selected, their combined operating airflow becomes the input for pad sizing.
2. Use only fans that operate at the same time
Some houses have fans in stages. For example, two fans may run at a lower temperature and four fans at extreme afternoon heat. Size the cooling pad for the maximum stage, when all four fans run. The pad must pass the highest air volume without excessive resistance.
Do not add HAF or air-circulation fan airflow to this calculation. HAF fans circulate air within the crop area; they do not exhaust air from the polyhouse and do not increase the required pad face area.
Choose a Suitable Cooling Pad Face Velocity
Pad face velocity means the speed of air moving straight through the visible front face of the wet pad. It is not the air speed measured in the crop rows.
For a typical cellulose cooling pad system, use 1.0–1.5 m/s as a practical planning range, subject to the pad manufacturer’s recommendation. The best value depends on pad thickness, flute angle, local summer conditions, fan pressure capability and desired cooling performance.
Pad face velocity | When it is generally useful | Main result |
|---|---|---|
0.8–1.0 m/s | Very hot/dry areas, long houses, thick pads, or where extra cooling margin is wanted | Larger pad area; lower resistance and more even air entry |
1.0–1.3 m/s | A conservative, common design range for many commercial vegetable and flower houses | Good balance of pad area, airflow and cooling |
1.3–1.5 m/s | When layout space is limited and fan static pressure is properly checked | Smaller pad area, but resistance and uneven wetting risk rise |
Above 1.5 m/s | Only if the pad specification and system design clearly support it | Greater pressure drop; cooling can reduce and dry patches become more likely |
A lower face velocity is usually safer than a higher one. A pad that is too small forces air through too fast. This raises pressure drop and can make the fan system deliver less air than expected. It may also cause more water carry-over, dry zones, or warm air entering near the top and corners.
Pad thickness also matters. A 100 mm pad and a 150 mm or 200 mm pad do not have the same resistance or saturation performance at the same air velocity. Confirm the recommended velocity for the exact pad model and thickness. Read how to choose cellulose cooling pad thickness before finalising the design.
Calculate the Required Active Pad Area
Use this formula:
```text
Pad area (m²) = Total operating fan airflow (m³/hour) ÷ 3,600 ÷ pad face velocity (m/s)
```
Or, when the fan capacity is already in m³/s:
```text
Pad area (m²) = Total operating fan airflow (m³/s) ÷ pad face velocity (m/s)
```
Worked example
Assume a fan-and-pad polyhouse has three exhaust fans. From the fan curve at the expected operating pressure, each fan delivers 15,000 m³/hour.
- Number of fans running at peak load: 3
- Airflow per fan at operating pressure: 15,000 m³/hour
- Total airflow: 45,000 m³/hour
- Convert to m³/s: 45,000 ÷ 3,600 = 12.5 m³/s
- Chosen face velocity: 1.25 m/s
Therefore:
```text
Required active pad area = 12.5 ÷ 1.25 = 10 m²
```
If the available pad height is 1.8 m:
```text
Required pad length = 10 ÷ 1.8 = 5.56 m
```
In practice, select a layout with at least this active face area. For example, a 1.8 m high pad that is about 5.6 m long gives approximately 10 m². It is sensible to allow some extra area where framing, end sections, access constraints or future performance loss may reduce the effective opening.
Do not calculate using the pad’s internal corrugated surface area. Only use the front face area exposed to incoming air: height × length.
Measure Active Area, Not Just the Frame Opening
The pad may be physically large but still have a smaller effective air-entry area. For accurate matching, deduct any portion blocked by the following:
- GI posts, strong frames and cross-bracing across the face
- Solid blank panels below or above the pad
- Pump pipes, filters or covers placed directly in front of the pad
- Poorly designed insect screens or dust screens
- Closed shutters or restricted intake openings
- Sections left dry, clogged with scale, or damaged
For example, a 6 m long × 1.8 m high pad has a gross face area of 10.8 m². If 0.8 m² is blocked by framing and blanking, the active pad face is only about 10 m². It is the 10 m² that should be compared with fan airflow.
Where a long uninterrupted pad wall is not possible, divide the required area across two intake sections. Keep the combined active area equal to or higher than the calculated requirement. Make water distribution, sump return and access equally reliable on both sections.
Avoid placing the pad only in a short central opening while the fans draw from a wide end wall. Air will favour the path of least resistance. Crops near the pad may receive a cold, humid air stream while corners receive warmer, slower air.
Check Pad and Fan Layout Before Ordering
Correct area alone does not guarantee uniform cooling. Air must travel through the house with as little bypass and short-circuiting as possible.
Put pads and exhaust fans on opposite ends
In a conventional long rectangular polyhouse, install the cooling pad on one end and exhaust fans on the opposite end. This creates a clear lengthwise airflow path through the crop.
Keep the house length realistic for the system design. As air crosses a long house, it picks up sensible heat from the roof, floor, crop and structure. The air near the exhaust end will normally be warmer than air near the pad, even when pad area is correct. Extra pad area cannot fully solve an excessively long airflow path.
Seal unwanted openings during pad operation
When fan-and-pad cooling is operating, outside air should enter mainly through the wet pad. Open doors, roof vents, torn insect net, loose side curtains and gaps around fans allow hot outside air to bypass the pad.
This can make the system look under-sized even where the calculation is correct. Check that:
- Fan shutters open fully when fans start.
- Non-running fan shutters close properly.
- Doors and service openings remain closed in peak cooling hours.
- Curtains, vents and other openings follow the intended control sequence.
- The pad wall has no large uncovered gaps.
Allow service access without blocking airflow
Provide a safe walkway to inspect headers, distribution pipes, the gutter and pump. However, do not place storage, fertilizer bags, crates or a permanent wall directly in front of the pad. A clear intake zone helps air spread over the full pad face.
Field Checklist: Test Whether Pad Area and Fans Are Matched
Run this checklist before summer and again during a hot afternoon when all fan stages are called.
- Confirm the maximum fan stage. Count every fan that runs together at peak temperature.
- Record fan operating airflow. Use the manufacturer’s performance data at expected static pressure. Do not rely only on free-air capacity.
- Calculate active pad requirement. Divide total airflow in m³/s by the selected pad velocity, preferably in the 1.0–1.5 m/s planning range.
- Measure installed active area. Multiply usable pad height by usable length. Deduct major obstructions and blanked portions.
- Check the fan-to-pad match. Installed active area should meet or exceed the calculation.
- Inspect pad wetting. The entire face should wet evenly soon after the pump starts. Dry streaks reduce effective cooling area.
- Look for bypass air. Smoke testing by a trained technician or simple inspection of curtains, doors and loose panels can reveal leaks. Use safe methods and never introduce smoke that can harm workers or crops.
- Compare temperatures at both ends. Place sensors near crop height, away from direct spray and sun. A temperature rise from the pad end toward the exhaust end is expected, but a very large difference suggests an airflow, shading, pad wetting or house-layout problem.
- Observe fan condition. Bent shutters, dirty blades, belt slip where applicable, poor motor performance and low voltage all reduce delivered airflow.
- Clean and maintain the pad. Algae, mineral scale and dust increase resistance. Follow a planned cellulose pad maintenance schedule, especially where borewell water has high mineral content.
Common Matching Mistakes and Their Effect
Mistake | What happens in the polyhouse | Practical correction |
|---|---|---|
Sizing pad from floor area alone | Pad may not match the installed fan duty | Calculate from total operating fan airflow |
Using fan free-air airflow | Actual airflow is overestimated | Use the fan curve at working static pressure |
Selecting the smallest possible pad | High velocity and pressure loss reduce performance | Increase active face area or review fan selection |
Ignoring pad thickness | Resistance and saturation are misjudged | Follow the specific pad technical data |
Counting gross frame size | Usable intake area is overstated | Deduct blocked and blanked sections |
Running fans with open bypass gaps | Hot air enters without being cooled | Seal gaps and follow the ventilation control sequence |
Poor water distribution | Part of the pad remains dry and ineffective | Level the header, clean holes and maintain pump flow |
Next steps
First, list the exhaust fans that run together at peak summer load and obtain their operating airflow figures. Then calculate the active cooling pad face area at a conservative target velocity, check the available wall dimensions, and confirm pad thickness with its technical data.
For material planning, you can review exhaust fan options, cellulose cooling pad specifications, and build a material kit with current item quantities and rates. Polyhouse Constructions supplies fan-and-pad polyhouse material kits and individual materials; the structure and cooling system should still be checked against local climate, crop and layout by a qualified designer or agronomist.
Frequently asked questions
What is the formula for cooling pad area for an exhaust fan?
Divide the total airflow of all exhaust fans running together, in m³/s, by the chosen pad face velocity in m/s. If airflow is in m³/hour, divide by 3,600 first. Use active pad face area, not the pad’s corrugated internal surface area.
Can I use one cooling pad size for different fan stages?
Yes, but size the pad for the highest stage, when the maximum number of fans runs together. At lower fan stages, air velocity through that same pad will simply be lower.
Is a larger cooling pad always better?
A modestly larger active pad area lowers air resistance and can improve cooling consistency. But it also needs more wall space, water distribution and maintenance, so it should be designed around the fan capacity and pad specification rather than made arbitrarily large.
Why is my polyhouse still hot even though the cooling pad is large enough?
Check whether fans are delivering their rated airflow under load, whether the pad is fully wet, and whether doors or gaps are allowing uncooled air inside. High outside humidity, inadequate shade, long house length and poor crop airflow can also limit the temperature reduction.
Should insect net be installed in front of a cooling pad?
An insect barrier may be required for crop protection, but it adds airflow resistance and can collect dust. Include its pressure loss in fan selection, keep it clean, and ensure the fan-and-pad system is designed as a complete airflow path.