How to Automate a Polyhouse Ventilation System by Temperature
Polyhouse Constructions Agronomy Desk · 13 Nov 2026
An automatic polyhouse ventilation system uses a temperature sensor and controller to operate side curtains, roof vents, exhaust fans or cooling equipment without waiting for a person to switch them on. The basic sequence is simple: when crop-zone temperature crosses a chosen set point, ventilation starts; when it falls sufficiently, the equipment stops or closes.
For reliable results, do not use one on/off temperature point alone. Build in a temperature gap between starting and stopping, operate equipment in stages, and include manual override and power-failure protection. The correct set points depend on crop, crop stage, outside weather, humidity and the type of polyhouse.
Start with the ventilation method in your structure
Temperature automation must suit how air moves through your protected structure. A naturally ventilated polyhouse (NVPH) removes heat mainly through side openings and roof vents. A fan-and-pad polyhouse creates controlled airflow with exhaust fans drawing air through wet cellulose pads. A nethouse relies on natural air movement and has fewer parts that can be automated.
Before selecting a controller, list the equipment you want it to operate.
Structure type | Equipment commonly automated by temperature | Main purpose | Important limitation |
|---|---|---|---|
Naturally ventilated polyhouse | Roll-up side curtains, roof vents, shade screen, circulation fans | Release trapped hot air | Natural ventilation depends on wind direction and wind speed |
Fan-and-pad polyhouse | Exhaust fans, pad pump, circulation fans, vents or shutters | Create measured airflow and evaporative cooling | Pads need adequate water quality, flow and regular maintenance |
Nethouse | Shade screen, misting or circulation fans where fitted | Reduce crop heat load | It cannot provide the same environmental control as a closed polyhouse |
If you are deciding between systems rather than retrofitting one, compare the operating approach in this guide to NVPH versus fan-and-pad polyhouses. In an NVPH, automated curtains can save labour and react faster to sudden sunny conditions. But they cannot cool incoming air below outdoor temperature in the way a properly designed fan-and-pad system can.
Components you need for temperature-based control
A working system has five layers: sensing, decision-making, power switching, movement or airflow, and safety. Weakness in any one layer makes automation unreliable.
1. Temperature and humidity sensor
Use a protected air-temperature sensor suitable for greenhouse conditions. A combined temperature and relative humidity (RH) sensor is usually more useful because high humidity changes the ventilation decision, especially in monsoon and winter.
Mount the primary sensor at crop-canopy height, away from direct sun, fogger spray, cooling-pad discharge and the hot air stream from a fan motor. Shield it from radiation while keeping air able to pass around it. In a long house, or in houses with separate climate zones, use more than one sensor and configure the controller to act on the average or the warmest representative zone.
Read the detailed guidance on where to place temperature and humidity sensors in a polyhouse. A sensor fixed near the roof can read several degrees higher than the crop zone on a sunny day. That may open curtains too early or run fans longer than required.
2. Climate controller or thermostat
The controller compares the measured temperature against the set points you enter. Choose a unit with enough relay outputs for current equipment and reasonable future expansion. For example, a small NVPH may need outputs for two curtain motors and a circulation fan. A fan-and-pad house may need separate outputs for multiple fan stages, pad pump, circulation fans, alarm and possibly a shade screen.
Useful controller functions include:
- Separate day and night temperature programmes
- Multiple fan or vent stages
- Adjustable differential or hysteresis
- Time delay between starting large motors
- High-temperature alarm output
- Temperature and RH display or data logging
- Manual/auto selector input
- Sensor fault warning
A simple thermostat can operate one fan, but it is rarely enough for a multi-stage commercial house. See the practical selection points in how to select a climate controller.
3. Actuators: the parts that move or switch
For side ventilation, an electric geared motor with a suitable roll-up mechanism can raise and lower the curtain. Fit upper and lower limit switches so the motor stops at the fully open and fully closed positions. The curtain pipe, gear and mounting brackets must be aligned properly; otherwise the motor may overload or wind the film unevenly.
For forced ventilation, the controller does not normally supply power directly to a large exhaust fan. It signals a contactor, relay or motor starter sized by a qualified electrician for the motor load. The starter then switches the fan. Fan shutters may open by airflow or use a separate actuator, depending on the design.
Use an exhaust fan sized for the structure and crop requirement. Fan quantity and capacity should be calculated first; automation cannot correct an undersized ventilation system.
4. Electrical panel and protection
Keep the controller and electrical switching gear inside a clean, dry panel. The panel should include correctly rated isolators, breakers, contactors, overload protection, earthing and surge protection as applicable. Use suitable cable size and weather-protected cable routing.
Motors draw more current during starting. Staging fan starts a few seconds apart reduces sudden electrical load and helps prevent nuisance trips. Ask a licensed electrician to design and commission the panel. Never bypass overload protection simply because a fan trips; identify the cause first.
5. Backup and alarms
A hot polyhouse can become risky quickly during a summer power cut, particularly where plants are large and canopy transpiration is high. Provide a high-temperature alarm that can alert the farm manager. Depending on your crop value and location, consider generator, inverter or solar-backed supply for essential controls, alarms and selected ventilation equipment.
Also provide manual handles, manual switches or a safe release arrangement for curtains. Automation should reduce routine work, not leave the crop helpless when a sensor, controller or motor fails.
Set the temperature logic before wiring the system
The most important automation work is deciding what happens at each temperature. Start from the crop’s preferred temperature range, then make the response gradual. Tomato, capsicum, cucumber, flowers and nursery crops do not all need identical settings. Even within one crop, a young nursery plant and a fruiting mature plant may need different targets.
A useful principle is stage the response from least intensive to most intensive:
- Open side curtains or roof vent partly.
- Open them further if temperature continues to rise.
- Start circulation fans if fitted.
- Start the first exhaust-fan stage in a fan-and-pad house.
- Start additional fans as temperature rises further.
- Run the pad pump only when fans are creating airflow and evaporative cooling is likely to help.
- Trigger a high-temperature alarm if the final stage cannot control the temperature.
Do not copy the sample values below without adjustment. They are an example of the logic, not a universal crop programme.
Condition at the crop sensor | Example controller action | Why it helps |
|---|---|---|
Temperature reaches crop target | Open side curtains to a partial position | Begins heat release with low energy use |
Temperature rises about 1–2°C above target | Open curtains wider; start circulation fan if needed | Increases air exchange and reduces hot pockets |
Temperature rises a further 1–2°C | Start exhaust fan stage 1 | Adds forced removal of hot air |
Temperature remains high | Start fan stage 2; enable pad pump in fan-and-pad house | Increases cooling capacity in steps |
Temperature reaches alarm limit | Send alarm; check power, water, fan operation and vent movement | Calls for immediate human attention |
Use hysteresis to stop rapid cycling
Hysteresis means using different temperatures for switching on and switching off. For example, if a fan starts at 30°C and stops at 29°C, it will not switch repeatedly when the reading fluctuates around 30°C. A differential of roughly 1–2°C is a common starting range, but needs field adjustment.
For curtains, use timed movement or position feedback. A controller may open the curtain for a short period at each stage rather than command it to fully open immediately. This creates partial openings. Limit switches remain essential as the final physical protection.
Use a delay before accepting a temperature change
Short spikes happen when direct sun reaches a sensor, a door opens, or a worker sprays water nearby. Configure a short time delay or averaging function so that equipment responds to a sustained temperature rise. Do not make the delay so long that summer heat builds up before fans start.
Control logic for naturally ventilated polyhouses
In an NVPH, the automation priority is normally to move air out through side curtains and roof vents while avoiding rain entry and crop damage from harsh wind. A basic arrangement may have independently controlled curtains on the two long sides.
A practical curtain sequence
On a warm, dry day, open the leeward side first or open both sides in stages, based on the site’s usual wind pattern. On very hot days, full side opening and roof ventilation may be required. At night, close gradually as temperature falls, while retaining enough opening to avoid excess condensation if weather permits.
A better controller uses more than temperature alone:
- Temperature high: open curtains in stages.
- Rain detected: close roof vents or rain-exposed curtains to a safe position.
- Strong wind: limit opening on the windward side if the structure and crop require it.
- High RH at a safe temperature: open enough ventilation to remove moisture rather than keeping the house sealed.
- Low night temperature: close curtains, subject to humidity needs.
A rain sensor for roof-vent automation is particularly useful where a sudden shower can wet crop foliage, media or packed produce. Test its response before every monsoon season.
Avoid a common mistake: closing every vent as soon as the temperature falls. In cool, humid mornings or winter nights, a completely sealed house can collect condensation. This encourages leaf wetness and disease pressure. The right minimum opening depends on outside conditions and crop sensitivity.
Control logic for fan-and-pad polyhouses
Fan-and-pad automation needs coordinated control. Fans create negative pressure; air should enter through the pad wall or designed inlet, not through many unintended gaps. Keep doors closed during operation and repair damaged polyfilm, loose shutters and openings that short-circuit airflow.
A basic multi-stage example is:
- At the first high-temperature stage, start exhaust fan 1.
- If temperature does not come down after the selected delay, start fan 2 and then further fan stages as designed.
- Enable the pad pump after airflow is established and temperature is above the cooling threshold.
- Stop the pad pump before or together with fans as temperature falls, according to the controller programme.
- Keep circulation fans independent where possible, as they may be useful even when pad cooling is not running.
Do not run pads simply because the day is warm. In humid monsoon conditions, evaporative cooling may provide limited temperature drop while pushing RH too high. Use your temperature and RH records to decide when pad operation is beneficial. The controller can include an RH lockout or a more advanced humidity/VPD-based strategy.
Fan stages should match the calculated air volume requirement. Use this separate guide to calculate exhaust fan size for a fan-and-pad polyhouse before selecting equipment or set points.
Installation and commissioning checklist
Install the automation only after mechanical parts move freely and electrical protection is complete. Commission it during a moderate-weather period if possible, not for the first time on the hottest May afternoon.
- Inspect vents and curtains. Check film fastening, curtain pipes, gears, cables, brackets and travel path. Remove obstructions.
- Mount and verify sensors. Place them at representative crop height in radiation shields. Compare readings with a checked reference thermometer.
- Set manual override. Confirm each curtain motor, fan, pump and circulation fan works safely in manual mode.
- Confirm travel limits. Test fully open and fully closed limit switches at low risk. Mark safe curtain positions if the controller uses timed movement.
- Programme initial stages. Enter conservative day and night set points, hysteresis and time delays. Record every value in the panel logbook.
- Test interlocks. Check that the pad pump cannot run unexpectedly without required airflow, and that rain or wind inputs give the intended vent response.
- Simulate alarms. Safely test the high-temperature alarm, sensor-fault response and power restoration behaviour.
- Observe for several days. Compare inside temperature, RH and crop appearance at morning, midday and evening. Adjust one setting at a time.
Check electrical terminals, curtain alignment and sensor cleanliness regularly. Dust on a radiation shield, algae around a wet sensor location, loose fan belts or a sticking shutter can make a well-programmed system perform badly.
Common faults and their likely causes
Problem | Likely cause | First check |
|---|---|---|
Fans start and stop every few minutes | No hysteresis, very short delay, sensor in unstable airflow | Increase differential and relocate or shield sensor |
Curtains open at the wrong time | Sensor exposed to sun or roof heat; wrong controller schedule | Check sensor location and day/night programme |
One curtain rolls unevenly | Misalignment, loose fixing or worn gear | Inspect mechanical assembly before increasing motor power |
Pad pump runs but house remains hot | Fans undersized, poor airflow path, pad issue or high outside humidity | Check fan capacity, shutters, leaks and pad wetting |
Controller reading is unrealistic | Sensor wet, dirty, damaged or out of calibration | Clean, compare and recalibrate or replace sensor |
Next steps
First, map your existing ventilation equipment and decide whether you need curtain automation, fan staging, or both. Then choose a controller with enough outputs, install sensors correctly, and commission the system with staged set points rather than one aggressive trigger temperature.
If you are planning a new structure or upgrading its coverings and ventilation materials, you can build a material kit and view this week’s rates. For individual retrofit components and compatible protected-cultivation materials, see the materials catalogue. Keep a daily climate log for the first few weeks; it is the fastest way to refine your settings for local summer, monsoon and winter conditions.
Frequently asked questions
Can I automate polyhouse ventilation with only one thermostat?
A single thermostat can switch one small fan or one simple curtain circuit, but it gives limited control. For commercial crops, a climate controller with multiple stages, hysteresis, alarms and manual override is usually more practical.
What temperature should start automatic polyhouse ventilation?
Set the first stage near the upper end of your crop’s preferred daytime range, then adjust from actual crop and climate records. The correct point varies with crop, maturity, solar radiation, season and the temperature difference between inside and outside.
Should side curtains close automatically at night?
Usually they should close partly or fully when night temperature falls below the crop requirement. However, leave or create sufficient ventilation when humidity and condensation are a concern, rather than sealing the house blindly.
Can a temperature controller operate both exhaust fans and cooling pads?
Yes, provided it has suitable outputs and the electrical panel uses correctly rated contactors and protection. Programme the pad pump as part of a fan-and-pad sequence, not as an isolated temperature switch.
What happens if the temperature sensor fails?
A good controller should show a sensor-fault warning and raise an alarm where configured. Maintain manual controls and inspect the climate readings daily, because a failed sensor can otherwise leave fans or curtains in the wrong position.